Ductwright HVAC Calculator

Duct sizing, airflow, fan laws, loads, superheat and subcooling. Offline.

Free to try for 7 days, then unlock Pro once. No subscription.

Coming soon to Google Play
Ductwright on an Android phone: Duct size

What it does

Ductwright is an HVAC and sheet metal calculator for HVAC technicians, installers, sheet metal workers and apprentices. It works like a hardware calculator: a galvanized-grey chassis, real keys and a clear LCD, with each answer labelled so you know what you are reading.

Airflow and ducts

  • Airflow = area × velocity, in cfm or L/s, with conversion between them
  • Velocity from airflow and duct, or from velocity pressure
  • Round duct sizing by equal friction, 0.1 in wg per 100 ft unless you set another rate
  • Friction rate for a given airflow and duct
  • Rectangular duct: the other side for a round size, and the round equivalent diameter

Fans and loads

  • Fan laws: new airflow, static pressure and brake power for a speed change
  • Sensible heat from airflow and temperature difference, in BTU/h, tons and kW
  • Airflow required for a given load

Fittings and sheet metal

  • Offset travel and angle
  • Radius elbow throat, heel and centreline lengths at any angle
  • Round taper flat pattern: slant height, pattern radii and sweep angle
  • Bend allowance, bend deduction and outside setback, with K-factor presets for soft aluminium and steel

Air and refrigerant

  • Dew point and wet bulb from dry bulb and relative humidity
  • Saturation temperature from gauge pressure for R410A, R32, R454B, R134A, R290 and R22
  • Superheat above dew and subcooling below bubble, with glide shown for blends

Works the way you do

  • Inches, cfm, ft/min, °F and psig, or millimetres, L/s, m/s, °C and bar
  • A results strip shows every solved value at once
  • 10 memories, a tape of your calculations, reference tables and a key guide
  • Large keys you can hit with gloves on

Worked examples

How it's calculated

Every trade key and the formula behind it, as shown in the app's key guide. A second legend is the shifted function.

CFM L/sAirflow / Convert airflow
Stores the typed airflow (cfm, or L/s in metric), or solves Q = Area × Velocity from the duct and velocity; shifted converts between cfm and L/s.
Vel VPAir velocity / Velocity pressure
Stores the typed velocity (ft/min, or m/s in metric), or solves V = Q ÷ Area. Shifted: a typed velocity pressure gives V = 4005 × √VP (or √(Pv ÷ 0.6) m/s); blank gives the velocity pressure of the stored velocity.
Duct RectRound duct size / Rectangular duct
Stores the typed round diameter, or sizes round galvanized duct by equal friction: D = (0.109136 × Q^1.9 ÷ friction)^(1 ÷ 5.02), friction 0.1 in wg per 100 ft unless stored. Shifted stores side A, or solves side B for the stored diameter.
Frict EqØFriction rate / Equivalent diameter
Stores the typed friction rate (in wg per 100 ft, or Pa/m), or solves it for the stored airflow and duct. Shifted stores side B, or gives the round equivalent De = 1.30 × (A × B)^0.625 ÷ (A + B)^0.25.
Fan LawFan speed / New fan speed
Stores the present fan rpm; shifted stores the new rpm. Blank steps through the fan laws: flow × N2/N1, static pressure × (N2/N1)², brake power × (N2/N1)³.
ΔT LoadTemperature difference / Sensible load
Stores the air temperature rise or drop (°F, or K in metric). Shifted gives sensible heat Q = 1.08 × cfm × ΔT BTU/h (1.2 × L/s × ΔT W), then tons and kW; a typed load solves the airflow instead.
Fitting PatternFitting / Taper pattern
Stores a typed offset (or angle). Blank gives offset travel √(O² + L²) and angle, and radius elbow throat r × θ, heel (r + A) × θ and centreline (r + A ÷ 2) × θ. Shifted stores the length, or lays out a round taper: slant, pattern radii and sweep 360 × R ÷ Rp.
Bend KBend allowance / K-factor and radius
Stores the typed sheet thickness (or angle). Blank gives bend allowance (π × θ ÷ 180) × (Ri + K × T), bend deduction and outside setback. Shifted stores a typed K-factor, or a radius typed with a unit key; blank steps K 0.33 and 0.44.
Temp DP/WBAir temperature / Dew point and wet bulb
Stores the dry-bulb temperature. Shifted stores the typed relative humidity; blank gives dew point (Magnus) and wet bulb (Stull 2011, valid 5 to 99 % RH and −20 to 50 °C).
Refrig SH/SCRefrigerant / Superheat or subcooling
A typed gauge pressure (psig, or bar in metric) gives the saturation temperature; blank steps through R410A, R32, R454B, R134A, R290 and R22. Shifted: a typed line temperature gives superheat above dew or subcooling below bubble.

Results are computed from the formulas shown for each function and are provided for reference only. They do not replace a load calculation, duct design or the equipment maker's data. Verify every result against the code in force and the authority having jurisdiction, and follow safe refrigerant handling practice. The developer accepts no liability for loss or damage arising from use.

Get Ductwright

Free to try for 7 days, then unlock Pro once. No subscription. Works offline, no ads, no account.

Coming soon to Google Play

Ductwright support · Ductwright privacy policy

In het Nederlands

Kanaalmaten, luchtdebiet, ventilatorwetten, oververhitting en onderkoeling.

Ductwright is een rekenmachine voor installatie- en plaatwerk: voor monteurs klimaattechniek, koeltechnici, plaatwerkers en leerlingen. Hij werkt als een echte rekenmachine: een verzinkt grijze behuizing, echte toetsen en een helder LCD-scherm, met bij elk antwoord een label zodat u weet wat u leest.

Gratis 7 dagen proberen, daarna eenmalig Pro ontgrendelen. Geen abonnement.